Product Introduction
EPRO MMS6120 is a dual-channel bearing vibration measurement module. It monitors the vibration conditions of bearings in a wide range of rotating equipment, thereby ensuring smooth operation and prolonging the equipment's lifespan.

Technical Specifications
|
Manufacture |
EPRO |
|
Model |
MMS6120 |
|
Part Number |
MMS6120 |
|
Description |
Dual Channel Bearing Vibration Monitor |
|
MoOrigin |
Germany |
|
Dimension |
24*17*6cm |
|
Weight |
0.23kg |
Product Details
| MMS6120 |
|
Sensor inputs: Continuously adjustable with the configuration software.Min. dynamic input voltage:311 mVppfor 100 % measuring rangeMax. dynamic input voltage:9500 mVppfor 100 % measuring range(allowing measuring ranges:Vams=5 .. 100 mm/s correspondingwith +25 ... +500 ym vibration displacement for the transducers PR 9266 /..PR 9268 /..) 10..1000 Hz (according to VDl 2056 / |
DIN 45666/IS0 3945)Filtercharacteristics accordinglyOther frequency ranges selectable from5/10 . 50 . 1000/1600 Hz. For each of the two input channels aseperate, buffered lifting coil currentoutput is available to compensate themechanical sag of the transducer; theseoutputs are galvanically seperated fromall the system voltages as well as fromthe system suppiy voltage and they areopen and shortcircuit proof.Available current: 0 ... 8 mA; configurable in steps of 40 μA. |
"danger"; make or brake mode. Keypuise (1 puls per rev.)input forsystem control (only requested for orderanalysis purposes)24 V logic Two, one for each channelNot used in standard applications.0 .. 10 Volts |
Module and sensor supervision:
Channel clear/circuit fauit sensingsystem; the internal modul supervisioncircuitry continuously supervises thefollowing functions:Sensor signal is within a preset window.Cabling between sensor and modul is ok(no shortcircuit, no break).System supply voltages are within presetwindows.Configuration and parameter settingsare correct.Measuring range not overloaded.
Internal temperature not overloaded.System watch dog.During changing from a sensor malfunc-tion into the ok status or after switchingon the modul a delay time of 15 sec. isoperable."Channel clear" is visualised on the frontof the module by means of a green LED;this LED switches off during a "channelfault"; during the delay time the LEDflashes.The channel status is also indicated via a binary output, separately for each of thetwo channels.Umax- 48 V dc= 100 mAmaxThe reasons for a "channel fault" indi-cation can be read out via the communi-cation buses; which enables service per-sonel to take immediate corrective mea-sures.
Signal outputs at the connecting strip:
Terminal strip on rear side:acc. to DIN 41 612 , version F 48 MRS 485 communication interface.
Two independent current outputs:
One for each channel; outputs are pro-portional to the selected operatingmode.
0/4..20 mA;configurable,open- andshortcircuit proofPermissible load: < 500 OhmsAccuracy: 16 bit resolution; ±1 % of fullrange
Settling time: 0 .. 10 sec.; configurablein increments of 1 sec. separately foreach channel.
Two independent voltage outputs:
One for each channel; outputs are pro-portional to the selected operating mode(e. g. shaft vibration amplitude S1..)0 ... +10 Volt, open and shortcircuit proofLoad resistance: > 10 kOhmResolution: 8 bit
Two independent voltage outputs:
One for each channel; proportional tothe AC part of the signal are available;one for each channel.open and shortcircuitproof.Nominal range: 0 ... 20 VppPermissable load: > 10 kOhmFrequency range: 0,1 Hz..5 Khz(± 20 %/-3 dB)
Connection Diagram