SB510 3BSE000860R1 is a battery charger that works together with a single battery package, for example, SB522. Use these two modules for the current supply of the processor module RAM in the event of a mains supply dropout.
The capacity expressed in time of backup depends on the application. Please refer to the actual Advant Controlled documentation. Use two sets (SB510 and SB522) to double the backup time.
SB510 3BSE000860R1 is positioned in a controller subrack to interface with the backplane bus and the battery. Mains supply connected via a module front connector.
Module included in the backup power supply system for RAM
Connectable to mains supply 100 -230V a.c. or d.c
Three modes of operation: battery recharging and trickle charging from a mains supply, and battery discharging
Fits NiCd battery unit SB522
The mains supply input provides fusing and other adequate protection. The input energy is converted into an internal unit supply by a controlled current generator for battery charging. The current generator produces a current adapted to the mode of operation: recharging, which takes approximately 10 hours after power-up or battery replacement, or trickle charging. During recharging, an LED FC on the module frontlights up.
Diagnostic functions continuously supervise the operation. Errors and other statuses are indicated by module front LEDs. The information available on the backplane is further processed by the system status functions.
At installation, insert the module in the subrack first. Then connect the power supply (Xll)
Input:
DataMains supply:110-230 V a.c.; variation -15 to +10%; ripple <15%
Max. power:110 -230 V dc.; -20 to +20%; ripple 25 VA
Indicators:
LEDs on module front:
F, Fault (red) Low-charging current, low 5 V supply (lP is supposed to indicate converter in operation)
IP, Input Power (green, Mains supply available, converter in operation
BP, Battery Powered (ylw) Mains supply not available, discharging of battery
BF, Battery Fault (red) Discharged/unconnected battery, short-circuit or interruption in battery, cold battery at start.
FC, Fast Charging (ylw) Indicates recharging after power-up or battery replacement (l0 hours).